ASCII - Command ANOUT2    
Syntax Transmit ANOUT2 [Data]    
Syntax Receive ANOUT2 <Data>   Available in  
Type Variable rw   MMI Yes
ASCII Format Integer8   CANBus Object Number 387F (hex)
DIM     PROFIBUS PNU 1695 (dec) IND = 33 (dec)
Range 0 .. 9   DPR 895 (dec)
Default 0    
Opmode All   Data Type Bus/DPR Integer8
Drive State -   Weighting  
Start Firmware 3.00    
Configuration Yes   Last Change of this Object 2.9
Function Group analog I/O   EEPROM Yes
Short Description Configuration of the Analog Output 2

Description

Only S700

Configuration of analog output 2. The actual value is read via MONITOR2. The output provides various analog command values or actual values, depending on the selection in the operator software. Output resistor 2.2kOhm.
Status function description
0 off no output at monitor output 2
1 n_actual output of actual speed value
(10 V = VLIM)
2 I_actual output of actual current value
(10V = IPEAK)
3 n_cmd output of speed setpoint
(10V = VLIM)
4 I_cmd output of current command value
(10V = IPEAK)
5 PE output of position error
(10V = PEMAX)
6 slot output of the DPR-value throuht the monitor 2
(with DPR-Slotkarte). ab FW >= 5.38
7 PFB the actual position is set to the analog output. The scaling refers to the modulo-value ERND-SRND.

the output value is calculated by:
ANOUTx = 10V * (PFB-SRND)/(ERND-SRND)

if SRND is 0, the range of ERND is +/-10V. If SRND is unequal 0, the range is output is asymmetric.

with PFB=SRND the output value is = 0 and PFB=ERND the output vale is = 10V.
8 U_const=x the constant value of AN2TRIG (in mV) is set to analog output 2
9 I2T output of I2T
(10V = 100%)