Screen page "Speed"
Use the default values for the motor as a starting point for optimization.
Cycle
time of the speed controller: 250 µs
SpeedLimit
ASCII: VLIM |
Default: 3000 rpm |
valid for OPMODES 0+1 |
Limits the motor speed. The maximum value also depends on the used motor
and encoder.
Rotary Direction
ASCII: DIR |
Default: 1 |
valid for all OPMODES |
Fixes the direction of rotation of the motor shaft, referred to the polarity
of the setpoint.
Make changes only while the amplifier is disabled + reset.
This parameter is not available, if a SERCOS interface is built-in.
After
changing the rotary direction the hardware limit switches have to be exchanged.
Standard
setting: right-hand (cw) rotation of the motor shaft (looking at the shaft
end), with:
positive voltage on terminal X3/4 (+ ) against terminal X3/5
( - ) or
positive voltage on terminal X3/6 (+ ) against terminal X3/7 (
- )
Setp. Ramp+
ASCII: ACC |
Default: 10 ms |
valid for OPMODES 0+1 |
Limits the rate of increase of the internal setpoint processing during
acceleration to the speed limit (valid for both directions). A jump or
step in the setpoint that is provided will be turned into a smoother, more
favorable transition. As long as the ramp time is less than the mechanically
limited rise time of the system, the response time of the system will not
be negatively affected.
The ramp time settings are still effective if the
limit-switches are activated.
Depending on the setting of the parameter
ACCUNIT, acceleration time or ramp gradient will be set.
Setp. Ramp
ASCII: DEC |
Default: 10 ms |
valid for OPMODES 0+1 |
Limits the rate of decrease of the internal setpoint processing during
braking to the zero speed (valid for both directions). A jump or step in
the setpoint that is provided will be turned into a smoother, more favorable
transition.
As long as the ramp time is less than the mechanically limited
fall time of the system, the response time of the system will not be negatively
affected. In most cases the Setp.ramp+ and Setp.ramp can be set to the
same value.
The ramp time settings are still effective if the limit-switches
are activated.
Depending on the setting of the parameter ACCUNIT, acceleration
time or ramp gradient will be set.
Overspeed
ASCII: VOSPD |
Default: 3600 rpm |
valid for all OPMODES |
Determines the upper limit for the motor speed. If this limit is exceeded,
the servo amplifier switches into the overspeed fault condition (error
message F08).
Emergency ramp
ASCII: DECSTOP |
Default: 10 ms |
valid for all OPMODES |
The braking ramp for emergency braking. This braking ramp is used if the
message n03, following error or n04, response monitoring occurs, as well
as on the activation of a hardware or software limit-switch.
Dis Ramp
ASCII : DECDIS |
Default : 10 ms |
Valid for all OPMODES |
If the output stage is disabled (by removal of the hardware or software
enable), the internal speed setpoint is run down to 0 along this ramp. When
the speed has fallen below 5 rpm the output stage is disabled.
This ramp
is only effective for motors that have a brake configured.
KP
ASCII: GV |
Default: 1 |
valid for OPMODES 0+1 |
Determines the proportional gain (also known as AC-gain). Increase the
value up to the level where the motor starts to oscillate, and then back
it off until the oscillations have clearly stopped. Typical values for
this setting are between 10 and 20.
Normalization: at KP = 1 and a control
deviation of v_cmd -v_act = 3000 rev/min the instrument delivers the peak
current.
Tn
ASCII: GVTN |
Default: 10 ms |
valid for OPMODES 0+1 |
Determines the integration time constant. Smaller motors permit shorter
integration times; larger motors or high moments of inertia in the load
usually require integration times of 20 ms or more. With Tn = 0 ms the
I-component is switched off.
PID-T2
ASCII: GVT2 |
Default: 1 ms |
valid for all OPMODES |
Affects the proportional gain (P-gain) at medium frequencies. It is often
possible to improve the damping of the speed control loop by increasing
PID-T2 to about Tn/3. The setting is made, if required, after the basic
setting of KP and Tn.
Feedback
ASCII: GVFBT |
Default: 0,4 ms |
valid for all OPMODES |
If necessary, the time constant for the PT1-filter in the actual speed
feedback (tachometer smoothing) can be altered. This may improve the step
response and smoothness of running, particularly for very small, highly
dynamic motors.
PI-PLUS
ASCII: GVFR |
Default: 1 |
valid for OPMODES 0+1 |
This parameter only effects when the I-component is switched on (GVTN ¹ 0).
With the default setting, the speed controller functions as a standard
PI-controller with slight overshoot in the step response. If PI-PLUS is
reduced to 0.65, the overshoot is avoided and the actual value approaches
the setpoint slowly.
Optionally, you can reduce Tn. This makes the drive
stiffer for the same step response.